    铠装移开式交流金属封闭开关设备概述 Overview

    本装置系户内金属铠装抽出式开关设备(以下简称开关设备),系3.6-12 千伏三相交流50Hz 单母线及单母线分段系统的成套配电装置主要用于发电厂,中小型发电机送电、工矿企事业配电以及电业系统的二次变电所的受电、送电及大型高压电动机起动等。实行控制保护、监测之用,本开关设备满足IEC298、GB3906 等标准要求,具有防止带负荷推拉断路器手车、防止误分合断路器、防止接地开关处在闭合位置时关合断路器、防止误入带电室、防止在带电时误合接地开关的联锁功能,既可配用VSI 真空断路器,又可配用ABB 公司的VD4 真空断路器。实为一种性能优越的配电装置。

    This equipment is indoor metal armoring with drawable switchgear (hereafter refer to as switchgear. 3.6-12kilovolt three phase AC 50Hz single bus bar and the single bus bar subsection system's omplete electricity distribution equipment is used in the power plant, small and medium-sized generator power transmission, industry and mining business power distribution as well as electrical industry system's second transformer substation's electric take-over , power transmission and largescale high pressure motor starting and so on. The purpose is to control, protect and monitor. This switch equipment is up to the standard of IEC298、GB3906 and can prevent the charge from pushing and pulling the breaker, from opening and closing the breaker, from insulation with electricity by mistaken, from earthed switch closing the breaker ,from opening the switch's interlock when it with electricity mistakenly. It can not only use with VSI vacuum circuit-breaker, but with ABB Corporation's VD4 vacuum circuit-breaker. It is indeed a kind of power distribution equipment with superior performance.

    铠装移开式交流金属封闭开关设备使用环境条件 Use environmental conditions

    1. 正常条件

    a. 周围环境空气温度:上限,+40℃ 下限,-10℃

    b. 海拔:1000M

    c. 相对环境湿度:日平均相对湿度不大于95%,月平均相对湿度平均不大于90%;

    d. 地震:烈度不超过8 度。

    e. 周围空气应不受腐蚀性或可燃气体、水蒸汽等明显污染。

    f. 无严重污秽及经常性的剧烈振动,严酷条件下严酷度设计满足1 类要求。

    2. 特殊工作条件:

    * 在超过GB3906 规定的正常的环境条件下使用时,由用户和制造厂协商。

    1. Normal condition

    a. Surrounding air temperature:-10℃~ +40℃

    b. Altitude : 1000M

    c. Relative environment humidity: The daily relative humidity average is not higher than 95%, the monthly relative humidity average is not than higher 90%

    d. Earthquake : The intensity does not exceed 8 degree.

    e. The surrounding air without corrosive or flammable gas or water vapour.

    f. Without a lot of dirtiness and regular fierce vibration, under the severe condition, the intensity meets the first kind requirement.

    2. special working conditions

    * When it is used beyond the normal environmental condition stipulated in the GB3906, the user should consult with the manufacture.

    铠装移开式交流金属封闭开关设备主要技术参数 The main technical parameters

    铠装移开式交流金属封闭开关设备主要技术参数

    铠装移开式交流金属封闭开关设备结构简介 Structure Introduction

    开关设备按GB3906-91 中的铠装式金属封闭开关设备而设计。整流器体是由柜体和中置式可抽出部件(既手车)两大部分组成,见图

    1。柜体分四个单独的隔室,外壳防护等级为IP4X,各小室间和断路器室门打开时防护等级为IP2X。具有架空进出线、电缆进出线及其它功能方案,经排列、组合后能成为各种方案形式的配电装置。本开关设备可以从正面进行安装调试和维护,因此它可以背靠背组成双重排列和靠墙安装,提高开关设备的安全性、灵活性,减少了占地面积。

    The switch equipment is designed according to GB3906-91 metal armoring seal switch equipment. The rectifier body is made up of the cabinet body and draw-out parts (namely handcart) placed in the middle. See charter 1. The cabinet divides into four separate rooms, the outer covering protection grade is IP4X,when each small room and the circuit breaker is opened, the protection grade is IP2X.It can suspend the inlet, outlet line, cable’s inlet, outlet line and other function plan. After arranged and combined, it can become each kind of plan form of the power distribution equipment. This switch equipment may be installed and maintained from the frontage, therefore it may compose the dual arrangement back to back and be installed against the wall, improving the switch equipment’s security and flexibility and making full use of the occupying area.

    开关设备结构图 Switchgear structure diagram

    开关设备结构图

    开关柜外形尺寸图 Switchgear Dimensions

    开关柜外形尺寸图

    A 手车Handcar

    手车骨架系采用薄钢板经CNC 机床加工后经铆、焊而成的。根据用途,手车可分为断路器手车、电压互感器手车、隔离手车、计量

    手车等等,相同规格的手车能方便互换。手车在柜内有隔离位置、试验位置和工作位置,每一位置均设有定位装置,以保证手车处于以上

    位置时不能随便移动、而移动手车时必需要解除联锁。

    The framework of handcart is made of steel sheet through the procession of CNC machine tool and rivet welding. According to the application, the handcarts can

    be divided into circuit breaker hand-cart, voltage transformer handcart, isolating handcart and metering handcart, etc. The handcarts of the same specification can be

    exchanged conveniently. In the cabinet, the handcart has isolating position, testing position and operating position, each of which is designed with a location device to

    assure that the handcart can’t move easily at the above-mentioned positions, while the interlock must be unlocked to move the handcart.

    B 母线室Bus chamber

    母线从一个开关柜引至另一开关柜,通过分支母线和静触头盒固定。扁平的分支母线通过螺栓连接于静触头盒和主母线,不需要任何其它的线夹或绝缘子联接。当用户和工程特殊需要时,母线排上的联接螺栓可用绝缘和端帽封装。在母线穿越开关柜隔板时,用母线套管固定。如果出现内部故障电弧,能限制事故蔓延到邻柜,并能保障母线的机械强度。

    The bus is led from one switch cabinet to another one and fixed with static contact box through branch bus. The flat branch bus is connected through the bolt to the static contact box and main bus, not needing any other line clamps or insulators. When there is special demand of the clients or the project, the connecting bolt on the

    bus bar can be encapsulated with insulation and end cap. When the bus crosses the baffle of the switch cabinet, fix it with bus bushing, so that, if there is any internal fault arc, it can prevent the fault spreading to another cabinet and can guarantee the me-chanical strength of the bus.

    C 电缆室Cable chamber

    电缆室内可安装电流互感器、接地开关、避雷器以及电缆、并在其底部配制开缝的可卸铝板,以确保现场的施工方便。

    Inside the cable chamber, the current transformer, grounding switch, arrester and cable can be installed, and on the bottom is designed slotted removable aluminum

    sheet to assure the convenient siteconstruction.

    开关柜外形尺寸图 Switchgear Dimensions

    开关柜外形尺寸图

    D 继电器仪表室Relay instrument chamber

    继电器仪表室用于安装各类继电器、仪表、信号指示、操作开关等元器件。此外可根据用户要求在仪表室顶部增加小母线室,可敷设

    十六路控制小母线。

    Relay instrument chamber is used to install all kinds of components, such as relays, instruments, signal indicator and operating switch, etc. In addition, it’s available to add a small bus chamber on the top of the instrument chamber according to the demand of the clients, and set 16 lines to control the small bus.

    泄压装置Pressure releasing device

    在手车室、母线室、电缆室的上方设有泄压装置,当断路器或主母线、电缆室内发生内部故障电弧时,伴随电弧的出现,开关柜内部气压上升,达到一定的压力后,顶部装置的压力释放金属板将被自动打开,释放压力和排泄气体,以确保操作人员和开关柜安全。

    On the handcart chamber, bus chamber and cable chamber is installed pressure releasing device. When there is internal fault arc in the breaker, main bus or inside the cable chamber, and with the appearance of electric arc, the internal pressure in the switch cabinet rises. After it rises to a certain pressure, the pressure releasing metal sheet of the top device will be opened automatically, and the pressure and the gas are released to guarantee the safety of the operator and the switch cabinet.

    锁扣结构Latching device

    中门与柜体之间的联接采用锁扣结构,并配以提升机构,使中门开启更为方便,当中门处于关闭状态时,其与柜体的联接强度更好,增强了有效抗击内部燃弧故障的能力。

    Latching device is used to connect the central exit and cabinet body, and the lifting device is also designed to make it more convenient to open the central exit.

    When the central exit stays closed, the connecting strength with the cabinet body is the best and the capability against the internal arcing fault effectively is strengthened.